Cable size calculator

Find the minimum cable section so the voltage drop stays under the allowed limit (usually 3 % for lighting, 5 % for motors). Enter the current, the line length and the maximum percentage; the tool suggests the next standard section.

Minimum section
3.31 mm²
Recommended standard section
4 mm²

Indicative result: always verify against the standards and the installation method on site.

Formula

S = (k × ρ × L × I × cos φ) / ΔU (k = √3 three-phase, 2 single-phase)

Good to know

  • Based on voltage drop; also check the current-carrying capacity (heating) for the installation method.
  • ρ ≈ 0.0225 Ω·mm²/m for copper, 0.036 for aluminium.