ATEX marking and equipment selection

Where a gas, vapour or dust can explode (fuel station, paint shop, flour silo, solvent store), every motor, sensor, junction box or light fitting must be made for that zone. Describe the zone: the tool gives the category, protection level, group and temperature to respect. Or paste the marking read on a device’s nameplate: it says point by point whether it fits. The third tab checks an intrinsically safe loop (barrier, cable, sensor).

Example of a suitable marking
II 2G Ex db IIB T3 Gb
Minimum ATEX category
II 2G
Equipment protection level (EPL)
Gb
Equipment groups accepted
IIB · IIC
Highest temperature class
T3 (≤ 200 °C)
Types of protection allowed
Ex ia · Ex ib · Ex ma · Ex mb · Ex da · Ex db · Ex eb · Ex pxb · Ex pyb · Ex qb · Ex ob
Usual types of protection for this equipment in this zone
Ex db · Ex eb · Ex pxb

On a variable speed drive, the motor must be certified for that supply (often with PTC sensors wired to a protection relay): the plate or certificate says so.

An aid for reading markings (Directive 2014/34/EU, IEC 60079-0 and 60079-14). Zone classification and the final choice of equipment are for a competent person, with the device’s ATEX or IECEx certificate.

Indicative result: always verify against the standards and the installation method on site.

Publicité

Formula

Gas zones0→1G (Ga), 1→2G (Gb), 2→3G (Gc)
Dust zones20→1D (Da), 21→2D (Db), 22→3D (Dc)
Temperature, gassurface T≤auto-ignition T
Temperature, dustsurface T≤min(⅔ cloud T ; 5 mm layer T−75 K)

Good to know

  • Normal ambient temperature of the equipment: −20 °C to +40 °C. Beyond that, the allowed range is written on the plate (Ta or Tamb).
  • An “X” after the certificate number means specific conditions of use: they are in the manual and must be followed.
  • For a dust layer thicker than 5 mm, the allowed temperature is lower: see IEC 60079-14.

Reading an ATEX marking, item by item

Example: II 2G Ex db IIB T4 Gb. “II”: equipment for surface industries (“I” is for mines). “2G”: category 2, for gases. “Ex db”: the type of protection, here a flameproof enclosure. “IIB”: the gas group the device is made for. “T4”: its surface never exceeds 135 °C. “Gb”: the equipment protection level (EPL).

For dust, the temperature is written in degrees: II 2D Ex tb IIIC T135°C Db. The plate also carries the CE mark, the Ex symbol in a hexagon, the notified body number and the certificate number.

Zones and categories

Zone 0 (gas) or 20 (dust): the explosive atmosphere is present continuously or for long periods, for example inside a tank or silo. Category 1 equipment is needed (EPL Ga or Da).

Zone 1 or 21: it can occur in normal operation, around a filling or transfer point. Category 2 at least (Gb or Db).

Zone 2 or 22: it only occurs after an incident, and briefly. Category 3 is enough (Gc or Dc). A higher category always suits a less dangerous zone, never the other way round.

Temperature: the most common trap

Every gas ignites by itself on a hot enough surface: its auto-ignition temperature, given in the safety data sheet (section 9). The equipment temperature class (T1 = 450 °C … T6 = 85 °C) must stay below it.

For a dust, two values matter: the cloud ignition temperature (keep two thirds) and that of a 5 mm layer (subtract 75 °C). The lower of the two is the limit. A motor covered in flour runs hotter: regular cleaning is part of safety.

An intrinsically safe loop (Ex i): five comparisons

In intrinsic safety the energy is limited so much that no spark can ignite the gas. The limit is set by the barrier or isolator outside the zone (values Uo, Io, Po, Co, Lo); the field device accepts Ui, Ii, Pi and adds its own Ci and Li.

The loop is correct when Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi, and when Ci plus the cable capacitance stays under Co, and Li plus the cable inductance under Lo. The cable is what limits the length: about 200 pF and 1 µH per metre when its data sheet is not known.

Frequently asked questions

+Can IIC equipment go in a IIA or IIB zone?

Yes. IIC also covers IIB and IIA, and IIB covers IIA. The reverse is forbidden: IIA equipment must not go where there is hydrogen (IIC).

+Can category 3 equipment go in zone 1?

No. Category 3 (Gc or Dc) is for zones 2 and 22 only. Zone 1 or 21 needs at least category 2.

+What is the difference between ATEX and IECEx?

ATEX is the European directive (CE mark and Ex hexagon), IECEx the international certification scheme. Both use the same IEC 60079 markings (Ex db, IIB, T4, Gb). The site specification says which one is required.