AWG to mm² converter
Drawings and machines from the US or Asia often give wire sizes in AWG, while cable elsewhere is sold in mm². Pick an AWG size to get its cross-section and the metric size to order, or enter a size in mm² to find the closest AWG.
- 12 AWG → AWG wire cross-section
- 3.31 mm²
- Conductor diameter
- 2.05 mm
- Equivalent standard IEC size (or next up)
- 4 mm²
- 2.5 mm² → Closest AWG
- 13 AWG (2.62 mm²)
AWG ↔ mm² table
| AWG | mm² | Ø mm | IEC ≥ |
|---|---|---|---|
| 4/0 | 107.2 | 11.684 | 120 |
| 3/0 | 85.029 | 10.405 | 95 |
| 2/0 | 67.431 | 9.266 | 70 |
| 1/0 | 53.475 | 8.251 | 70 |
| 1 | 42.408 | 7.348 | 50 |
| 2 | 33.631 | 6.544 | 35 |
| 3 | 26.67 | 5.827 | 35 |
| 4 | 21.151 | 5.189 | 25 |
| 5 | 16.773 | 4.621 | 25 |
| 6 | 13.302 | 4.115 | 16 |
| 7 | 10.549 | 3.665 | 16 |
| 8 | 8.366 | 3.264 | 10 |
| 9 | 6.634 | 2.906 | 10 |
| 10 | 5.261 | 2.588 | 6 |
| 11 | 4.172 | 2.305 | 6 |
| 12 | 3.309 | 2.053 | 4 |
| 13 | 2.624 | 1.828 | 4 |
| 14 | 2.081 | 1.628 | 2.5 |
| 15 | 1.65 | 1.45 | 2.5 |
| 16 | 1.309 | 1.291 | 1.5 |
| 17 | 1.038 | 1.15 | 1.5 |
| 18 | 0.823 | 1.024 | 1 |
| 19 | 0.653 | 0.912 | 0.75 |
| 20 | 0.518 | 0.812 | 0.75 |
| 21 | 0.41 | 0.723 | 0.5 |
| 22 | 0.326 | 0.644 | 0.5 |
| 23 | 0.258 | 0.573 | 0.5 |
| 24 | 0.205 | 0.511 | 0.5 |
| 25 | 0.162 | 0.455 | 0.5 |
| 26 | 0.129 | 0.405 | 0.5 |
| 27 | 0.102 | 0.361 | 0.5 |
| 28 | 0.081 | 0.321 | 0.5 |
| 29 | 0.064 | 0.286 | 0.5 |
| 30 | 0.051 | 0.255 | 0.5 |
Indicative result: always verify against the standards and the installation method on site.
Publicité
Formula
Good to know
- Theoretical cross-sections of a solid conductor; a stranded wire of the same gauge is close.
- The IEC size shown is the standard value equal or just above: always check the current rating for the installation method.
How AWG works
AWG (American Wire Gauge) is a number: the larger it is, the thinner the wire. Every 3 gauges the cross-section roughly doubles; every 6, the diameter doubles.
Above 1 AWG come 1/0, 2/0, 3/0 and 4/0 (“one aught, two aught…”), then large cables in kcmil.
Handy equivalents
14 AWG ≈ 2.1 mm² (use 2.5 mm²), 12 AWG ≈ 3.3 mm² (use 4 mm²), 10 AWG ≈ 5.3 mm² (use 6 mm²), 8 AWG ≈ 8.4 mm² (use 10 mm²).
For signals: 18 AWG ≈ 0.82 mm² (use 1 mm²), 20 AWG ≈ 0.52 mm² (0.75 mm²), 22 AWG ≈ 0.33 mm² (0.5 mm²).
Frequently asked questions
+What is 12 AWG in mm²?
3.31 mm². The next standard metric size up is 4 mm².
+What AWG is 2.5 mm²?
Between 14 AWG (2.08 mm²) and 13 AWG (2.63 mm²); the closest is 13 AWG, and in practice you use 12 AWG to stay above.
+Why does AWG go down as the wire gets thicker?
The number came from how many times the wire was drawn through a die: the more it was drawn, the thinner it got and the higher the number.