Skip to content

AWG to mm² converter

Drawings and machines from the US or Asia often give wire sizes in AWG, while cable elsewhere is sold in mm². Pick an AWG size to get its cross-section and the metric size to order, or enter a size in mm² to find the closest AWG.

12 AWG → AWG wire cross-section
3.31 mm²
Conductor diameter
2.05 mm
Equivalent standard IEC size (or next up)
4 mm²
2.5 mm² → Closest AWG
13 AWG (2.62 mm²)
AWG ↔ mm² table
AWGmm²Ø mmIEC ≥
4/0107.211.684120
3/085.02910.40595
2/067.4319.26670
1/053.4758.25170
142.4087.34850
233.6316.54435
326.675.82735
421.1515.18925
516.7734.62125
613.3024.11516
710.5493.66516
88.3663.26410
96.6342.90610
105.2612.5886
114.1722.3056
123.3092.0534
132.6241.8284
142.0811.6282.5
151.651.452.5
161.3091.2911.5
171.0381.151.5
180.8231.0241
190.6530.9120.75
200.5180.8120.75
210.410.7230.5
220.3260.6440.5
230.2580.5730.5
240.2050.5110.5
250.1620.4550.5
260.1290.4050.5
270.1020.3610.5
280.0810.3210.5
290.0640.2860.5
300.0510.2550.5

Indicative result: always verify against the standards and the installation method on site.

Publicité

Formula

d (mm)=0.127×92^((36−n)/39)
A=π×d²/4

Good to know

  • Theoretical cross-sections of a solid conductor; a stranded wire of the same gauge is close.
  • The IEC size shown is the standard value equal or just above: always check the current rating for the installation method.

How AWG works

AWG (American Wire Gauge) is a number: the larger it is, the thinner the wire. Every 3 gauges the cross-section roughly doubles; every 6, the diameter doubles.

Above 1 AWG come 1/0, 2/0, 3/0 and 4/0 (“one aught, two aught…”), then large cables in kcmil.

Handy equivalents

14 AWG ≈ 2.1 mm² (use 2.5 mm²), 12 AWG ≈ 3.3 mm² (use 4 mm²), 10 AWG ≈ 5.3 mm² (use 6 mm²), 8 AWG ≈ 8.4 mm² (use 10 mm²).

For signals: 18 AWG ≈ 0.82 mm² (use 1 mm²), 20 AWG ≈ 0.52 mm² (0.75 mm²), 22 AWG ≈ 0.33 mm² (0.5 mm²).

Frequently asked questions

+What is 12 AWG in mm²?

3.31 mm². The next standard metric size up is 4 mm².

+What AWG is 2.5 mm²?

Between 14 AWG (2.08 mm²) and 13 AWG (2.63 mm²); the closest is 13 AWG, and in practice you use 12 AWG to stay above.

+Why does AWG go down as the wire gets thicker?

The number came from how many times the wire was drawn through a die: the more it was drawn, the thinner it got and the higher the number.