Surge protector (SPD) sizing

A storm or the switching of a large load sends surges of several thousand volts that destroy PLC power supplies, drive boards and HMIs. The surge protector diverts them to earth. Describe your site: the tool suggests the type and ratings, then checks that the wiring really protects.

SPD type
Type 2
Poles (three-phase network)
3P+N, 3+1 connection
Minimum Uc
275 V
Current In / Imax (8/20 µs)
20 / 40 kA
Voltage actually seen by the equipment
2 kV
Limit (80 % of equipment withstand)
1.2 kV
Maximum connection length
0 m

✗ Not enough: shorten the SPD leads, choose a lower Up or add a type 3 SPD close to the equipment.

✗ Equipment more than 10 m away: the surge can double by reflection. Add a type 3 SPD (or a low-Up type 2) in the equipment’s panel.

In TT: SPD upstream of the RCD, “3+1” connection (L–N varistors, N–PE spark gap), otherwise the RCD trips on every surge.

Incoming supplyL1L2L3NMain switch / breakerFeeders ↓SPD disconnector (backup)SPDType 2Surge protectorEarth baraba + b ≤ 50 cm (ideal), 1 m maximumPLC, drive, HMI> 10 m: 2nd SPD (type 3) close to the equipment

Indicative result: always verify against the standards and the installation method on site.

Publicité

Formula

Up seen=Up+1 kV/m×(a+b) ≤ 0.8×Uw (equipment withstand)

Good to know

  • 230/400 V network. Uc: 275 V in TT and TN, 440 V in IT. The In/Imax currents are the usual maker ranges for each exposure.
  • 1 kV per metre of wire: order of magnitude for a 10 kA (8/20 µs) surge in a wire of about 1 µH/m.
  • Protect the SPD with the breaker or fuses specified by its manufacturer.

Where does a surge come from?

Lightning does not have to strike the plant: a hit on the line, a pylon or the ground a few hundred metres away induces a surge in the cables. Network switching and starting large motors also create surges, smaller but frequent.

Electronics handle these peaks badly: a PLC 24 V supply, a drive input stage or an RS485 port break down from about 1.5 kV. A well-chosen, well-wired surge protector brings the surge below that level.

Type 1, type 2, type 3: which one?

Type 1: withstands part of the direct lightning current (10/350 µs wave, Iimp ≥ 12.5 kA per pole). Required at the origin of the installation when the building has a lightning rod, advised when the supply arrives by overhead line in a very exposed area.

Type 2: the most common. It diverts induced surges (8/20 µs wave, In and Imax). It goes in the main switchboard and in distant sub-panels.

Type 3: fine protection with a low Up, as close as possible to sensitive equipment (PLC, industrial PC, HMI). Only installed in addition to a type 2 upstream.

Surge protectors are coordinated in cascade: the first absorbs the energy, the last lowers the residual voltage.

The 4 values on the datasheet

Uc, maximum continuous voltage: at least 275 V in TT and TN, 440 V in IT, otherwise the SPD ages and heats.

In and Imax (kA, 8/20 wave): the discharge capacity. The more exposed the site, the higher (20, 40 or 65 kA Imax).

Up, protection level (kV): the voltage left behind the SPD. The lower, the better the equipment is protected.

The disconnector: breaker or fuse required by the maker, to isolate the SPD at end of life without cutting the whole installation. A signalling contact can report “SPD failed” to the PLC.

The 50 cm rule (the most forgotten)

During a surge, each metre of wire adds about 1 kV because of its inductance. An SPD with Up = 1.5 kV connected with 1.5 m of wire lets about 3 kV through: the PLC still burns.

The sum of lengths a (phase/neutral to the SPD, through its protection) + b (SPD to the earth bar) must stay under 50 cm, and 1 m at most. Short, straight cables, no loops, connected to the panel earth bar.

If the equipment is more than 10 m from the SPD, the surge can double by reflection in the cable: add a type 3 SPD in its panel.

Don’t forget signal lines

Surges also enter through communication and measurement cables: RS485 / Modbus buses, Ethernet between buildings, outdoor 4-20 mA sensors and PT100 probes. DIN-rail signal surge protectors exist for each.

In TT, install the SPD upstream of the RCD in a “3+1” arrangement, otherwise the RCD trips at every storm. After a violent storm, check the cartridge indicators and replace those at end of life.

Frequently asked questions

+Where should the SPD go in the panel?

At the head, right after the main switch or breaker (upstream of the RCD in TT), with its disconnector, and as close as possible to the earth bar: a + b ≤ 50 cm.

+Type 1 or type 2 for a plant?

Type 1 + 2 if the building has a lightning rod or a very exposed overhead supply; otherwise a type 2 in the main switchboard, plus type 2 or 3 close to distant PLCs and drives.

+How do I know an SPD has failed?

The cartridge indicator turns red and, if fitted, the signalling contact changes state. Check them after every storm and replace the cartridge.