Generator size calculator

A generator that is too small stalls when a pump starts; one that is too big costs more and clogs up when it runs at light load. Enter your loads by type and the biggest motor with its starting method: the tool gives the generator size to ask the supplier for, its current and the transfer switch rating.

Suggested generator
50 kVA
Minimum power calculated
49.5 kVA
Running load (kW / kVA)
31.7 / 35.7
Demand while the biggest motor starts
84.7 kVA
What sets the size
The running load
Generator rated current
72 A
Transfer switch rating
80 A

Indicative result: always verify against the standards and the installation method on site.

Publicité

Formula

RunningS≥reserve×max(P/0.8 ; S loads)
StartingS≥(S other loads+k×S motor)/2

Good to know

  • Assumptions: motors η 0.9 and cos φ 0.85; starting demand k = 6 direct on line, 2 star-delta, 3 soft starter, 1 with a drive; the generator accepts about twice its rating during the start.
  • This is a three-phase pre-sizing: have the size confirmed by the generator supplier, especially for large motors, lifts or sensitive loads.

Why motor starting matters so much

A motor started direct on line draws 6 to 7 times its current for a few seconds. The grid takes it easily, but a generator’s voltage drops: contactors drop out, drives trip, the generator stalls.

Starting the big motor in star-delta, with a soft starter or a drive cuts that demand sharply, and so the generator size.

kVA and kW: don’t mix them up

A generator is sold in kVA at cos φ 0.8: a 100 kVA set gives at most 80 kW. The tool checks both.

Keep a reserve (25 % by default): a generator always loaded at 100 % wears quickly, and your needs will grow.

Don’t oversize either

A diesel engine that runs for long periods below about 30 % load clogs up. If the load varies a lot, two smaller generators or soft starting are often better than one big set.

Frequently asked questions

+What size generator for a 7.5 kW borehole pump?

Direct on line with no other load, about 30 kVA; with a soft starter or a drive, about 15 kVA is enough. Enter your own values in the tool for your exact case.

+How do I convert generator kVA to kW?

Multiply by 0.8: a 60 kVA generator gives 48 kW.

+What rating for the transfer switch?

At least the generator rated current (and that of the main breaker on the mains side). The tool suggests the standard rating just above the generator current.