Short-circuit current calculator
The short-circuit current at the main switchboard sets the minimum breaking capacity of the circuit breakers. Enter the transformer power, the secondary voltage and its impedance voltage (ucc, on the nameplate, often 4 to 6 %): the tool gives the rated current and the maximum short-circuit current at its terminals.
- Maximum short-circuit current
- 22.7 kA
- Rated secondary current
- 909.3 A
Indicative result: always verify against the standards and the installation method on site.
Publicité
Formula
In=S/(√3×U)
Isc=In×100/ucc
Good to know
- Calculated with an infinite upstream network: this is the maximum value, on the safe side for choosing the breaking capacity.
- Away from the transformer, Isc falls with the cable impedance: calculate it for each feeder.