4-20 mA scaling calculator
A 4–20 mA sensor (pressure, temperature, level, flow) sends a current that the PLC analog card turns into an integer. Enter the sensor range and the card range: the tool gives the engineering value, the raw value expected in the PLC and the current, both ways. Handy to write the scaling (SCALE, NORM_X / SCALE_X) or to check a sensor with a multimeter.
- Engineering value
- 5
- PLC raw value
- 13824
- Signal
- 12 mA
- Percent of range
- 50 %
Indicative result: always verify against the standards and the installation method on site.
Publicité
Formula
Value=Vmin+(x−xmin)/(xmax−xmin)×(Vmax−Vmin)
Good to know
- Siemens S7-1200 / S7-1500: 0 to 27648 for the nominal range (4–20 mA or 0–10 V). Other cards use 0–4000, 0–10000 or 0–32000: check the card manual.
- A current below 3.8 mA or above 20.5 mA usually means a broken wire or a faulty sensor.