4-20 mA scaling calculator

A 4–20 mA sensor (pressure, temperature, level, flow) sends a current that the PLC analog card turns into an integer. Enter the sensor range and the card range: the tool gives the engineering value, the raw value expected in the PLC and the current, both ways. Handy to write the scaling (SCALE, NORM_X / SCALE_X) or to check a sensor with a multimeter.

Engineering value
5
PLC raw value
13824
Signal
12 mA
Percent of range
50 %

Indicative result: always verify against the standards and the installation method on site.

Publicité

Formula

Value=Vmin+(x−xmin)/(xmax−xmin)×(Vmax−Vmin)

Good to know

  • Siemens S7-1200 / S7-1500: 0 to 27648 for the nominal range (4–20 mA or 0–10 V). Other cards use 0–4000, 0–10000 or 0–32000: check the card manual.
  • A current below 3.8 mA or above 20.5 mA usually means a broken wire or a faulty sensor.