PT100 table: resistance ↔ °C
The PT100 is the most used temperature probe in industry: furnaces, heat exchangers, motors, processes. Measure its resistance with a multimeter and the tool gives the exact temperature, or enter a temperature to get the expected value, with the error the cable adds.
- Temperature
- 100 °C
- Sensitivity around this temperature
- 0.379 Ω/°C
- Error added by the cable in 2-wire
- +2.46 °C
Indicative result: always verify against the standards and the installation method on site.
Publicité
Formula
Good to know
- Callendar–Van Dusen equation from IEC 60751 (α = 0.00385), valid from −200 to 850 °C.
- 2-wire error: resistance of both copper wires added to the probe; in 3- or 4-wire it is compensated.
- Reference points: PT100 = 100 Ω at 0 °C, 107.79 Ω at 20 °C, 138.51 Ω at 100 °C.
How does a PT100 work?
It is a platinum wire (or film) whose resistance rises with temperature: 100 Ω at 0 °C, then about +0.385 Ω per degree. The PT1000 is 1,000 Ω at 0 °C: ten times more sensitive, so less affected by cable resistance.
The PLC (RTD card) sends a small current through the probe, measures the voltage, works out the resistance and then the temperature with the same equation as this tool.
2, 3 or 4 wires: why it matters
In 2-wire, the cable resistance adds to the probe: 20 m of 0.75 mm² cable adds about 0.9 Ω, more than 2 °C of error on a PT100. The tool computes this error.
In 3-wire, the card measures an extra wire and subtracts the cable resistance: the industry standard. In 4-wire the cable error disappears completely: used for precise measurement and long distances.
The wiring must be the same in the PLC card configuration (2, 3 or 4 wires) and in the actual cabling.
Accuracy: classes A and B
Class B: ± (0.3 + 0.005 × |t|) °C, i.e. ± 0.8 °C at 100 °C. Class A: ± (0.15 + 0.002 × |t|) °C, i.e. ± 0.35 °C at 100 °C. Choose the class for the accuracy your process needs.
Troubleshooting: wrong reading or fault
Disconnect the probe, measure it with a multimeter and compare with the expected value at room temperature (about 108 Ω at 20 °C for a PT100). Infinite resistance: open probe or wire, the PLC often shows its maximum or “wire break”. Near zero: short circuit.
Stable but offset reading: wrong type configured (PT100 instead of PT1000, or 0.00392 instead of 0.00385), uncompensated 2-wire, or an oxidised terminal adding resistance.
Jumping reading: moisture in the probe head, cable run alongside power or drive cables, shield badly connected. Use shielded cable, away from motor cables, shield earthed at the PLC end.
Frequently asked questions
+What resistance is a PT100 at 20 °C?
107.79 Ω (and 1,077.9 Ω for a PT1000). At 0 °C: 100 Ω; at 100 °C: 138.51 Ω.
+The PLC shows 850 °C or “wire break”, what now?
The loop is open: check the terminals, the cable and the probe with a multimeter. If the probe alone reads a normal value, the fault is in the cable or terminal block.
+PT100 or PT1000?
PT1000 for long 2-wire cables and low-power cards; PT100 remains the standard for industrial 3-wire RTD cards. What matters is that the card is configured for the right type.